(2) Applicable to the first-class protection for the A-class electronic infor-
mation systems power lightning protection;
(3) Modular design, good leak tightness, easy for installation and wiring;
(4) Use of temperature control circuit technology, built-in over current protection circuit avoid fire; Operation? indication, remote signal interface and? deterioration alarm indication functional, green (normal), red (failure);
(5) Dust-proof, anti-corrosion, explosion-proof, fire-retardant features;
(6) High-energy SPD, Let through current large and small Leakage current, especially applicable to poor lightning environment;
Technical parameters:
| Product Model |
DK-380AC80 |
| Product Name |
??span class="font6"> Type modular SPD |
| Protection level |
B class |
| Rated voltage Un(V) |
380V |
| Nominal discharge current In(kA) |
40kA(8/20?s) |
| Maximum discharge current Imax(kA |
80kA(8/20?s) |
| Voltage protection level Up(kV) |
??span class="font6">1.5kV(20kA?? 8/20?s) |
| Max.ContinuousOperatingVoltage Uc(V) |
385V |
| Action voltage(V) |
??span class="font6">620V |
| Response Time(ns) |
<20ns |
| Leakage current(?A) |
??span class="font6">30?A |
| Protected mode |
L-PE, N-PE(4P) |
| Deterioration indication |
Deterioration indication window? |
| Connecting wire cross-section |
SPDConnection cable:BVR-16mm2,grounding line:BVR-25mm2 |
| Working environment |
Temperature: -40degrees certigrade ~ +80 degrees certigrade, relative humidity <95% |
| Case Material |
Flame Retardant Materials |
| Installation location |
Master or second power distribution box, power supply into line-side. with standard 35mm trail |
Product installation and application:
(1) Used in the main or second power distribution system power supply first-class lightning protection, parallel installed in the building master power distribution box into line-side, to be used in Kevin connection;
(2) Applicable to TT, TN-S, TN-C, IT, etc.? power supply system;
(3) Applicable to the AC? power distribution equipment ?lightning protection, such as: communications, television broadcasting, computer room, automatic control, electrical and mechanical equipment and all distribution equipment;
(4) Suitable for indoor operation, if installed in the outdoor, it is important to the installation? waterproof anti-corrosion? shell;
(5) All wiring must be solid and reliable electrical connection;
(6) Lightning protection grounding should comply with standard? requirements, grounding line as far as possible, short and grounding resistance should be less than 10?.
?