(2) Applicable to the first-class protection for the A-class electronic information systems power lightning protection;
(3) The core of the device selected international brands, high reliability;
(4) Maximum discharge current up to 160, especially applicable to poor lightning environment;
(5) Kevin connection mode used, the residual voltage is extremely low, pro-tective value large, protected equipment safer; Modular components, easy installation, easy maintenance
(6) Using voltage-switching-type devices and the voltage limiting device combinational circuits, installation convenience, maintenance-free
(7) Applied to different power supply systemm, avoid happened the fire; Protective shell Level is IP2X, dust-proof, anti-corrosion, explosion-proof, fire-retardant features;
Technical parameters:
| Product Model |
DK-380AC150 |
| Product Name |
B type power surge protector |
| Protection level |
B class |
| Rated voltage Un(V) |
380V |
| Nominal discharge current In(kA) |
80kA??/span>8/20μs??/span> |
| Maximum discharge current Imax(kA |
160kA??/span>8/20μs??/span> |
| Voltage protection level Up(kV) |
≤1.5kV??/span>20kA 8/20μs??/span> |
| Max.ContinuousOperatingVoltage Uc(V) |
385V |
| Action voltage(V) |
≥620V |
| Response Time(ns) |
<20ns |
| Leakage current(μA) |
≤30μA |
| Protected mode |
L-N-PE??/span>3+1??/span> |
| Deterioration indication |
Working, fault indication, lightning count |
| Connecting wire cross-section |
SPDConnection cable:BVR-16mm2,grounding line:BVR-25mm2 |
| Working environment |
Temperature: -40 ??/span> ~ +80 ??/span>, relative humidity <95% |
| Case Material |
Iron box |
| Installation location |
Master or Branch power distribution box, power supply into line-side |
Product installation and application:
(1)Product installation and application used in the main power distribution system power supply first-class lightning protection, parallel installed in the building master power distribution box in-to line-side, to be used in Kevin connection;
(2) Applicable to TT, TN-S, TN-C, IT, etc. power supply system;
(3) Applicable to power distribution box , power distribution equipment box, communi-cations room, mobile base station and UPS power protection, etc.;
(4) All wiring must be solid and reliable electrical connection;
(5) Lightning protection grounding should comply with standard requirements, ground-ing line as far as possible, short and grounding resistance should be less than 10Ω