(1) Applicable to lightning region: at the junction of LPZ0 areas and LPZ1 district (B-class / ??/span> type)
(2) Modular design, good leak tightness, easy for installation and wiring;
(3) Used the "3+1" circuit structure, applicable to TT system;
(4) Operation indication, fault indication, telesignalling interface and alarm indication function. (add counter for customer require);
(5) Waterproof, dustproof, anti-corrosion, explosion-proof, fire-retardant and other functions, can be directly installed in open space;
(6) Through current large, residual voltage low, especially for poor lightning en-vironment.
Technical parameters:
| Product Model |
DK-380AC100 |
| Product Name |
A type power surge protector |
| Protection level |
B |
| Rated voltage Un(V) |
380V |
| Nominal discharge current In(kA) |
50kA??/span>8/20μs??/span> |
| Maximum discharge current Imax(kA |
100kA??/span>8/20μs??/span> |
| Voltage protection level Up(kV) |
≤1.5kV??/span>20kA 8/20μs??/span> |
| Max. Continuous Operating Voltage Uc(V) |
385V |
| Action voltage(V) |
≥620V |
| Response Time(ns) |
<20ns |
| Leakage current(μA) |
≤30μA |
| Protected mode |
L-N-PE??/span>3+1??/span> |
| Deterioration indication |
Deterioration indication window |
| Connecting wire cross-section |
SPDConnection cable:BVR-16mm2,grounding line:BVR-25mm2 |
| Working environment |
Temperature: -40 degrees certigrade ~ +80 degrees certigrade, relative humidity <95% |
| Case Material |
Waterproof aluminum box |
| Installation location |
Master or Branch power distribution box, power supply into line-side |
Product installation and application:
(1) Used in the main or first power distribution system power supply first-class lightning protection, parallel installed in the building master power distribution box into line-side, to be used in Kevin connection;
(2) Applicable to the AC power distribution equipment lightning protection, such as: communications, television broadcasting, computer room, automatic control, electrical and mechanical equipment and all distribution equipment;
(3) Waterproof function, indoor and outdoor can be operated;
(4) All wiring must be solid and reliable electrical connection;
(5) Lightning protection grounding should comply with standard requirements, grounding line as far as possible, short and grounding resistance should be less than10Ω.