DK-380AC80  C Type Power SPD

Click to enlarge image


Product introduction:

(1) Product introduction:Applicable to lightning  region: at the junction of LPZ1 or LPZ2 areas and  LPZ1 district  power lines lightning surge protection.

(2)Suitable for the floor distributing box power source line's  lightning surge protection

(3)Working instructions,external separated with a space to open device

(4)Use of temperature control circuit technology, built-in overcurrent pro-tection circuit to avoid fire;

(5)Waterproof, dustproof, anti-corrosion, explosion-proof, fire-retardant;

Technical parameters:

 

 

Product Model DK-380AC80
Product Name C Type SPD
Protection level C class
Rated voltage Un(V) 380V
Nominal discharge current In(kA) 40 kA??/span>8/20μs??/span>
Maximum discharge current Imax(kA 80 kA??/span>8/20μs??/span>
Voltage protection level Up(kV) 2.0 kV??/span>20kA   8/20μs??/span>
Max.ContinuousOperatingVoltage Uc(V) 385V
Action voltage(V) 620V
Response Time(ns) <20ns
Leakage current(μA) 30μA
Protected mode L-PE??/span>N-PE(2P)
Deterioration indication Working, fault indication
Connecting wire cross-section SPDConnection cable:BVR-10mm2,grounding line:BVR-16mm2
Working environment Temperature: -40 degrees certigrade ~ +80 degrees certigrade, relative humidity <95%
Case Material Iron box
Installation location Master or second power distribution box, power supply into line-side. 

Product installation and application:

(1)Used in the main or first power distribution system power supply second-class lightning protection, parallel installed in the building master power distribution box into line-side, to be used in Kevin connection;

(2)All wiring must be solid and reliable electrical connection;

(3)Lightning protection grounding should comply with standard  requirements, grounding line as far as possible, short and grounding resistance should be less than 10Ω. 

 

 


Related Keywords: Surge protector